The versatility of the C175 makes it ideal for a variety of applications.
- Continuous – A continuous rating has a typical load factor of 70% to 100% with no limit on the number of hours per
year. Typical peak demand is 100% of continuous rated kW for 100% of operating hours. Typical applications include
base load, utility or co-generation.
- Prime – A prime rating has a typical load factor of 60% to 70% with no limit on the number of hours per year. Typical
peak demand is 100% of prime rated kW with 10% overload available for emergency use for up to one hour in 12. Typical
applications include industrial, pumping, construction, peak shaving or co-generation.
- Standby – A standby rating has a typical load factor of 70% or less with variable load for about 200 hours per year.
Maximum expected usage is 500 hours. Typical peak demand is 80% of the standby rated kW with 100% of the rating available
for the duration of an emergency outage. Typical applications include building service standby and enclosure or
sheltered environments.
- Load Management – Used to shave peaks or contribute back to the utility.
